MHC Series - 500VA to 3000VA Description
Smart Online UPS Systems utilize true on-line operation to completely isolate connected equipment from all power problems, including subtle harmonic distortion. Dual conversion continually converts incoming AC into DC battery power, and then regenerate it back into a pure, clean sine wave AC. Winstream Power's Smart Online MHC/MHD 500-3000VA online, double conversion UPS protects critical server, networking or telecommunications equipment from blackouts, brownouts, voltage fluctuations and surges. Available in 6 output power ranges (500VA, 700VA, 1kVA, 1.5kVA, 2kVA, and 3kVA) continuously converts incoming AC to DC, then back to perfect sine wave AC output at 120V AC (+/-2%). Removes harmonic distortion, fast electrical impulses, frequency fluctuations and other hard-to-solve power problems not addressed by other UPS systems. True sine wave output and zero transfer time offers guaranteed compatibility with all equipment types. Includes 3 UPS supported AC outlets, RJ11/45 protection, and RS232 communication port for interface with power management software/remote shutdown. Battery support can be extended with the addition of multiple external battery packs to allow for virtually unlimited runtime. Comes complete with UPSilon 2000 Power Management Software included.
System Block Diagram
Features
Product Specifications
| Model |
|
MHC500* | MHC700 | MHC1000 | MHC2000 | MHC3000 |
|---|---|---|---|---|---|---|
| Output |
VA Rating | 500VA | 700VA | 1000VA | 2000VA | 3000VA |
| Watt (100~120V/220~240V) | 350W | 490W/450W | 700W | 1400W | 2000W | |
| Current (100~120V/220~240V) max. | 5A/2.2A | 6.4A/3A | 9.1A/4.3A | 18.2A/8.7A | 27.3A/13A | |
| Voltage | 100,110,120V/ 220,230,240V ± 2% | |||||
| Frequency | 50/60Hz Auto Select | |||||
| Waveform | Pure Sinewave | |||||
| Harmonic Distortion | Less than 3% at full load (Linear load) | |||||
| Input |
Voltage | 80V-145V/ 160V - 275V | ||||
| Frequency | 45 - 65Hz Auto select | |||||
| Runtime |
Full Load | 15 min | 5 min - 7 Min | |||
| Half Load | 45min. | 15min. | ||||
| Transfer
Time |
INV to Bypass /Bypass to INV | Less than 4 msec. (2 msec. min.)/ Zero-Cross Transfer | ||||
| Power Failure/ Recovery | 0 msec, to or from battery | |||||
| Battery |
Type | 12V/7AH Lead Acid maintenance free | ||||
| DC Voltage | 24 VDC | 36 VDC | 72VDC | 96VDC | ||
| Recharge Time | 5 - 8 hours | |||||
| Recharge Current | 1.5A (max.) | |||||
| Efficiency |
AC to AC | 85% min. | ||||
| Audible
Noise |
< 40 dBA | < 50
dBA |
||||
| Indicators |
LED Display | LINE, INV., BAT., BYPASS, FAULT, BAT./LOAD LEVEL | ||||
| Auto
Restart |
Yes | |||||
| DC Start
up |
Yes | |||||
| Protection |
Overload | >110% of full load with 15-20 sec. delay, 150% Immediately | ||||
| Over/Under Voltage at I/P or O/P | Inverter shutdown protection | |||||
| Phone Jack | RJ-11/RJ-45 | |||||
| Short Circuit | shut down and won't transfer to bypass output, will work normally again when short circuit be removed. | |||||
| Approved |
EMC/LVD (230V,50Hz) | EN50091-2/ EN50091-1 | ||||
| C-TICK (240V,50Hz) | AS-NZS 3548 | |||||
| Safety | TUV GS Mark EN50091-1-1,UL 1778,UL-2601-1,UL,CUL | |||||
| USA FCC (120V,60Hz) | FCC PART 15 | |||||
| CNS BSMI (110V,50/60Hz) | CNS 13438 | |||||
| IMMUNITY (120V/110V/100V,50/60Hz) | IEEE 587 CLASS A | |||||
| Computer
Interface |
LAN/RS232 Interface | Mains fail, battery low and remote shutdown UPS, RS232 communication | ||||
| Mechanical |
Dimensions (W*H*D)(mm) | 140x190x440 | 14x19x44 | 19x32x50 | 19x32x50 | |
| Net /Gross (kgs) | 12.3/13.8 | 14.8/16.3 | 32.4/36.4 | 38.2/42.2 | ||
| Environment |
Temperature | 0 - 40 |
||||
| Humidity | 0 - 95% Non-Condensing | |||||
MAIN POWER MHCM SERIES