PHOENIX ON-LINE UPS 1KV
Microprocessor control guarantees high reliability.
PWM Technology with IGBTs.
Wide Input Voltage Range.
Communication Port Selectable Smart RS-232 and Intelligent slot
for AS-400 and SNMP card.
Free Download Software from the internet for monitoring UPS status.
Optional external battery socket available for extended backup time.
Cold Start Function.
Auto self-testing system while turning on the UPS.
Modular design
Product Specifications
| MODEL | PHOENIX | 1K |
1KS* |
||
|---|---|---|---|---|---|
| CAPACITY | VA/W | 1000VA / 700W |
|||
| INPUT | Voltage Range | Based on load percentage (100%-80%/ 80%-70%/70%-60%/60%-0%) |
|||
| Low Line Transfer | 160VAC/140VAC/120VAC/110VAC ±5VAC |
||||
| Low Line Comeback | 170VAC±5VAC |
||||
| High Line Transfer | 300VAC±5VAC |
||||
| High Line Comeback | 285VAC ±5VAC |
||||
| Frequency Range | 45Hz~65Hz |
||||
| Phase | Single phase with ground |
||||
| Power Factor | >0.95 |
||||
| OUTPUT | Voltage | 220VAC/230VAC/240VAC |
|||
| Voltage Regulation | ±2% |
||||
| Frequency (Synchronized range) | 45~65Hz |
||||
| Frequency (Battery Mode) | 50/60Hz ± 0.2Hz |
||||
| Current Crest Ratio | 3:1 |
||||
| Harmonic Distortion | Tower Case | <3% THD (Linear Load) <6% THD (Non-Linear Load) |
|||
| Rack Case | <4% THD (Linear Load) <7% THD (Non-Linear Load) |
||||
| Output Waveform | Pure Sinewave |
||||
| EFFICIENCY | To AC Mode | 85% |
|||
| To Battery Mode | 83% |
||||
| BATTERY | Tower Case | Battery Type | 12V/7.2Ah | Depending on the capacity of external batteries | |
| No. of Batteries | 3 | ||||
| Backup Time | 5 minutes | ||||
| Recharge Time | 5 hours to 90% | ||||
| Charging Current | 1.0A | 7A | |||
| Charging Voltage | 41.1Vdc +/-0.6V |
||||
| Rack Case | Battery Type | 12V/7.2Ah | Depending on the capacity of external batteries | ||
| No. of Batteries | 3 | ||||
| Backup Time | 5 minutes | ||||
| Charging Current | 1.0A | 7A | |||
| Charging Voltage | 41.1Vdc +/-0.6V |
||||
| TRANSFER TIME | AC to DC | Zero |
|||
| Inverter to Bypass | 2.5ms (Typical) |
||||
| INDICATOR | Status | Load Level / Battery Level / Battery Mode / AC Mode / Bypass Mode / Fault |
|||
| AUDIBLE ALARM | Battery Mode | Sounding every 4 seconds |
|||
| Low Battery | Sounding every seconds |
||||
| Overload | Sounding twice every seconds |
||||
| Fault | Continuosly Sounding |
||||
| DIMENSION | Tower Case (DxWxH) mm | 400x145x220 |
|||
| Rack Case (DxWxH) mm | Rack UPS | 482.6x450x87 (w/ battery) |
|||
| Battery Pack | 482.6x450x87 |
||||
| WEIGHT | Tower Case (kgs) | 13kgs |
|||
| Rack Case (kgs) | 7kgs (w/ battery) |
||||
| ENVIRONMENT | Operating Temperature | 0-40C |
|||
| Relative Humidity | 20-90% (Non-Condensing) |
||||
| Noise Level | <45dB @1Meter |
||||
| INTERFACE | Smart RS-232 | Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX, FreeBSD, HP-UX and Mac |
|||
| SNMP (option) | Power management from SNMP manager and web browser |
||||
PHOENIX ON-LINE UPS