Global Navigation

Top Navigation

Left Navigation

Content

Phoenix TTN-V 10000

Product Specifications

 

MODEL  
10K
10KS
CAPACITY VA/W
10000VA/7000W
INPUT Phase
Single Phase with Ground
Frequency Range
50Hz:46~54Hz
Power Factor
>=0.98
Voltage Range
Base on load percentage
(100%-80% / 80%-70% / 70%-60% /60%-0%)
LineLow Transfer
176 +/- 3%VAC
Line Low Comeback
185 +/- 3%VAC
Line High Transfer
276 +/- 3%VAC
Line High Comeback
266 +/- 3%VAC
Output Phase
Single
Voltage
220VAC/230VAC/240VAC
Voltage Regulation
+/- 1%
Frequency (Synchronized Range)
46~54Hz
Frequency (Battery Mode)
50Hz +/- 0.5Hz
Current Crest Radio
3:1
Harmonic Distortion
2% THD (Linear Load)
6% THD (Non-Linear Load)
Output Wave
Pure Sine Wave
EFFICIENCY To AC Mode
>88%
To Battery Mode
>88%
BATTERY Battery Type
12V/9AH
Depending on the capacity of external batteries
Number of Batteries
20
Backup Time (Full Load)
5 Mins
Reacharge Time
8 hours to 90%
Charging Current (Max.)
2.0A
4.2A
Charging Voltage
274Vdc +/- 1%V
External Battery Type
N/A
12V/9AH
*20
TRANSFER TIME AC to DC
Zero
Inverter to Bypass
Zero
INDICATOR Blue Black LIght LCD for Real Time Status Display
Load Level / Battery Level / Battery Mode / AC Mode / Bypass Mode / Fault
AUDIBLE ALARM Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continously Sounding
DIMENSION UPS Case DxWxH (mm)
570x260x717
Battery Case DxWxH
570x260x717
WEIGHT Net Weight (kgs)
93 (with battery)
38
ENVIRONMENT Operating Environment
0~40 Degrees Centigrade, 20~90% relative humidity (non-Condensing)
Noise Level
<55dB @ 1 Meter
INTERFACE Smart RS-232
Windows 98/NT/2000/XP/2003, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX, FreeBSD, HP-UX, and MAC
SNMP (option)
Power Management from SNMP manager and web browser
 

Sidebar

Sidebar

Footer